当并联机组启动运行时,首先达到稳定状态的油机将通过发电机组断路器连接到母线,此时应同时合上该油机对应的接地接触器,当6个接地接触器中任意一台闭合时,其余接触器应保持断开状态。
When the parallel units start up and run, the first oil engine to
reach a stable state will be connected to the bus through the generator
circuit breaker. At this time, the corresponding grounding contactor of
the oil unit should be closed at the same time. When any one of the six
grounding contactors is closed, the rest of the contactors should remain
disconnected.
当该接触器故障无法合闸或已合闸的接地接触器故障时,此接触器应断开,同时闭合系统中任一台在线油机对应的真空接触器,保证某一时刻系统中只有1台发电机组的中性点经电阻器接地。
When the contactor fails to close or the ground contactor fails to
close, the contactor should be disconnected. At the same time, the
vacuum contactor corresponding to any on-line oil engine in the system
should be closed to ensure that only one neutral point of the generator
set in the system is grounded by the resistor at a certain time.
When the unit fails and needs to be disconnected from the bus, the
corresponding contactor is disconnected, and the vacuum contactor
corresponding to any on-line oil engine in the system is closed to
ensure that the grounding of the system is realized through the
grounding of the on-line oil machine